Five controllers on one pendulum, and the LQR that parks 0.36 rad off
Back to the control library hub
The result first: under the same 3 N torque LQR parks 0.36 rad off, LQI ends at 0.0008 rad with 6.1 N.

Situation
My old code base had an “adaptive PID” that updated its gains with kp += rate * error * error and
friends. No bound, no leak, no output limit. It balanced the demo pendulum, so nobody questioned it. When I
rewrote the library I wanted to know what it was actually worth next to a plain PID and next to the
textbook answer for an unstable plant, LQR.
Task
One inverted pendulum (m = 1 kg, l = 1 m, starting 0.10 rad off vertical, 1 ms fixed step, force limited to ±50 N) and a constant 3 N torque that none of the controllers model, switched on at t = 1 s. Five controllers, 10 s each, scored by the integral of |angle| and by the peak force.
Action
The old law is kept in the demo as-is so it can fail in public. The new ctl::AdaptivePid is bounded,
normalised, leaky and frozen while the actuator saturates. The LQR is designed on the linearised model
(solveDlqr, Q = diag(100, 1), R = 1); the LQI adds the angle integral as a third state with a weight of 500.
1. legacy adaptive law final -0.0317 rad cost 0.3460 rad*s peak |F| 110.00 N
2. fixed-gain PID final -0.0009 rad cost 0.0947 rad*s peak |F| 12.00 N
3. ctl::AdaptivePid final -0.0009 rad cost 0.0941 rad*s peak |F| 12.01 N
4. LQR on the linearised model final -0.3593 rad cost 3.1063 rad*s peak |F| 8.67 N
5. LQI (LQR + angle integral) final -0.0008 rad cost 0.2038 rad*s peak |F| 6.12 N
Row 1 asks for 110 N from a 50 N actuator, because nothing ever told it there was a limit. The bounded adaptive PID ends up where the fixed PID is and its gains come back to nominal (Kp = 120, Ki = 40, Kd = 12), which is what the leak is for.
Row 4 is the one I like. u = -Kx is optimal and gentle, but it has no integral action, so a constant
torque just parks the pole off vertical and it stays there. No choice of Q or R fixes that. Making the
integral part of the state (LQI) does, with less force than any PID row.
One embarrassing detail: the demo prints a paragraph under the table, and that paragraph says the LQR
parks “0.22 rad” off vertical. The number is a hard-coded 0.218 in a printf, not the value the run
computes (I don’t know any more where 0.218 came from). The measured row right above it says 0.3593. The asserted numbers are right; the
prose wasn’t asserted. The plot above comes from a copy of the demo with one CSV line added, built in /tmp.
Result
Under the same 3 N unmodelled torque, LQR settles 0.36 rad off vertical (peak force 8.67 N), while LQI ends at 0.0008 rad with a peak of 6.12 N. The old adaptive law commands 110 N against a 50 N limit and costs 3.7× what the plain PID does. Same table in the float build.
What I’d do next
Replace that hard-coded 0.218 with the value the run computes, and turn the commentary into assertions like the rest. Then the identification story: an LQR is only as good as its model, and the model on this page was handed to it (see RLS identification).