A brushed-motor drive stack (identify, tune, home, protect, fall back) run against a simulated H-bridge and encoder, six scenarios that assert their own numbers

#motor#control#simulation#cpp#testing
Last change2026-11-22: hub page, three STAR write-ups, re-run in double and float

DC motor drive on a simulated bench

The DC motor drive in numbers Identify, home, protect, fall back: six parameters found within 0.7 %, a chip fault handled in 1.05 ms, back-EMF speed 5.0 ms after the encoder dies. All on the simulated bench.

Bring-up from power-on: identification, hard-stop homing, then the first 30 rad move

After the control library I wanted one complete drive, not a loop in isolation: a small brushed motor on an integrated H-bridge with a quadrature encoder (4096 counts), the way it would sit on a board. That means everything around the PI that nobody draws in the block diagram. A CiA 402 state machine, so the drive can be enabled, faulted and reset properly. An identifier that measures the motor instead of trusting the datasheet. Homing against a hard stop. Protection: chip fault, I²t heating, stall. A back-EMF speed estimate for when the encoder dies.

There’s no board yet, so the plant is simulated: an H-bridge model with dead time, current ripple, heating and a bus, an encoder model with edge timing, on the brushed-motor model from my act library. One PWM period is 50 µs, the slow loop runs every 20th tick (1 kHz). The glue between drivers and control goes only through the driver interfaces, so the same code can later sit on hardware.

One executable, dc-motor, runs six scenarios, checks its headline numbers against the plant’s true state and exits non-zero if one is off. I re-built and re-ran it on 2026-11-22 in double and in float; both end with dc-motor: all expectations met.

The stories

#StoryResultStatus
1 Commissioning from a datasheet that's 50 % wrong
Enable, identify R, L, Kt, J, b and friction on the drive itself, re-tune from that, home on a hard stop, then move 30 rad
Six motor parameters identified within 0.7 % (datasheet off by 17-50 %) in 4.9 s; origin exact to the count, final error 0.7 counts Done
2 A load step, a disturbance observer, and a current sensor that can't tell direction
What a disturbance observer buys (and costs) under a 0.02 N·m step, and running the inner loop on a magnitude-only current signal
Observer: dip 2.49 -> 1.51 rad/s, recovery 18.0 -> 3.1 ms, at 2.8x the current noise; magnitude-only sensing holds the 3 A limit with 2.2x the speed noise Done
3 When it goes wrong: chip fault, a hot winding, a dead encoder
Three failure scenarios on the simulated drive: fault and reset through CiA 402, I²t derating on a pump, back-EMF fallback when the encoder line dies
Fault in 1.05 ms; winding peaks at 95.6 °C under a 110 °C limit with nothing tripped; dead encoder to back-EMF speed in 5.0 ms, still running Done

Still open

All of this is the simulator’s truth. A real motor’s back-EMF constant falls as the magnets warm and nothing re-checks it while running, and the host loop is sequential, so it never shows the interrupt preempting the 1 kHz task halfway through a step. The first real board will re-measure every number on these pages.