Power loops: a charger with no state machine, MPPT, and a sine an integrator can’t follow
The result first: the two-loop charger ends 99.5 % full against 90.0 % for the state machine; MPPT harvests 99.97 %.

Situation
Three power-electronics loops I’d only ever seen as application notes. Each one has a trick the app note states and doesn’t prove: a CC-CV charger doesn’t need a state machine, MPPT is a maximum to find and not a setpoint to hold, and a PI can’t follow a sine. I wanted the numbers.
Task
Charger: a 2.5 Ah lithium cell (35 mΩ, an RC branch with τ = 22.5 s), 1C charge to 4.2 V. Compare an explicit CC-CV state machine with two loops (current and voltage) always running, output = the minimum. MPPT: a 60-cell panel whose peak moves with irradiance and temperature, fixed voltage vs 76 % of Voc vs perturb-and-observe. Inverter: a 50 Hz grid with 1 % 3rd and 2 % 5th harmonic, 5 mH filter, 20 kHz loop, inject a clean sine of current.
Action
The state machine switches to CV on the terminal voltage. It doesn’t hunt on these cell parameters, but it ends at 90 % and steps the current command by the full 2.5 A in one sample at the switch, a transient the converter and the cell have to absorb:
1: explicit CC-CV state machine, switching on terminal voltage
final state of charge 90.0028 %
worst single-sample jump in the current command 2.5000 A
2: both loops always running, output is the minimum
final state of charge 99.4895 %
worst overvoltage 1.0835 mV
worst single-sample jump in the current command 0.0439 A
The minimum-of-two version takes longer (63 vs 45 minutes) because it actually fills the cell, and the handover is continuous by construction: no states, no hysteresis.
MPPT, over a run where irradiance and temperature change (a cloud, then a hot afternoon). The optimum is 31.8 V at 1000 W/m² and 25 °C but 28.4 V at 950 W/m² and 55 °C, so there is no setpoint to hold:
fixed voltage 92.7237 %
constant-voltage heuristic 94.6641 %
perturb and observe, coarse 99.9576 %
4: perturb and observe, 50 mV steps
tracking efficiency 99.9719 %
steady-state voltage dither 0.1000 V
Inverter: a PI alone, no feedforward, misses the fundamental amplitude by 56 % (an integrator has infinite gain only at DC). Adding a resonant term at 50 Hz fixes the fundamental, and a repetitive controller (one whole grid period of memory) also chases the harmonics:
1: PI plus grid-voltage feedforward
RMS tracking error 0.2252 A
2: PI + resonant term, with feedforward
RMS tracking error 0.1252 A
3: PI + repetitive controller, with feedforward
RMS tracking error 0.0666 A
total harmonic distortion 0.0845 %
Result
The two-loop charger ends at 99.5 % state of charge against the state machine’s 90.0 %, never more than 1.1 mV over the limit, with no command step (0.04 A vs 2.5 A). Perturb-and-observe with 50 mV steps harvests 99.97 % of the available energy against 92.7 % for a fixed voltage. On the grid-tie inverter, RMS current error falls 0.225 → 0.125 → 0.067 A and distortion sits at 0.085 % against a 5 % limit. All the same in the float build.

What I’d do next
The MPPT panel here has one peak. Partial shading gives a P-V curve with several local maxima, and perturb-and-observe happily climbs the wrong one. That’s the case worth simulating.